<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
Input type, <strong>ECL</strong> Key A2xx 11109<br />
Circuit Setting range Factory setting<br />
1 OFF / IM1 OFF<br />
Choice of pulse type signal applied to input S7. Possible in <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong><br />
as well as <strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong> controllers.<br />
OFF: No input.<br />
IM1: Pulse.<br />
Input type, <strong>ECL</strong> Key A3xx 11109<br />
Circuit Setting range Factory setting<br />
1 OFF / EM1 ... EM5 OFF<br />
Choice of M-bus signal from energy meter number 1 ... 5. Only possible<br />
in <strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong>.<br />
OFF: No M-bus signal acquired.<br />
EM1 ... EM5: Energy meter number.<br />
Pulse, <strong>ECL</strong> Key A2xx 11114<br />
Circuit Setting range Factory setting<br />
1 OFF / 1 ... 9999 OFF<br />
Set the value of the pulses from the flow / heat meter.<br />
OFF: No input.<br />
1 ... 9999: Pulse value.<br />
Flow or power limitation is based on pulse signals.<br />
Flow or power limitation is based on M-bus signal (<strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong><br />
controllers only).<br />
Example :<br />
One pulse can represent a number of litres (from a flow meter)<br />
or a number of kWh (from a heat meter).<br />