<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
<strong>A217</strong>.2 / <strong>A317</strong>.2 example a<br />
Indirectly connected DHW charging system with controlled heating temperature. DHW circulation through DHW tank or heat exchanger.<br />
S1<br />
S2 S3<br />
M1<br />
Special settings for type <strong>A217</strong>.2 / <strong>A317</strong>.2 example a:<br />
S5<br />
P1<br />
<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />
S4<br />
B<br />
The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for<br />
external circulation.<br />
P2<br />
Navigation: ID no.: Recommended setting:<br />
(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' 11054 OFF<br />
(External DHW circulation) MENU \ Settings \ Application: 'Cont. T control’ 11054 ON<br />
<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 15<br />
A1<br />
S6<br />
A<br />
S8<br />
P3<br />
<strong>Danfoss</strong><br />
87H2071.11