<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

5.7 Alarm<br />

Many applications in the <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> and <strong>310</strong> series have an<br />

alarm function. The alarm function typically activates relay 4 (<strong>ECL</strong><br />

<strong>Comfort</strong> <strong>210</strong>) or relay 6 (<strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong>).<br />

The alarm relay can activate a lamp, a horn, an input to an alarm<br />

transmitting device etc.<br />

The relay in question is activated as long as the alarm condition<br />

is present.<br />

Typical alarms:<br />

• Actual flow temperature differs from the desired flow<br />

temperature.<br />

5.7.1 Temp. monitor.<br />

Upper difference 11147<br />

Circuit Setting range Factory setting<br />

1 OFF / 1 ... 30 K OFF<br />

The alarm is activated if the actual flow temperature increases more than<br />

the set difference (acceptable temperature difference above the desired<br />

flow temperature). See also 'Delay'.<br />

OFF: The alarm function is not active.<br />

1 ... 30 K: The alarm function is active if the actual temperature<br />

gets above the acceptable difference.<br />

Lower difference 11148<br />

Circuit Setting range Factory setting<br />

1 OFF / 1 ... 30 K OFF<br />

The alarm is activated if the actual flow temperature decreases more than<br />

the set difference (acceptable temperature difference below the desired<br />

flow temperature). See also 'Delay'.<br />

OFF: The alarm function is not active.<br />

1 ... 30 K: The alarm function is active if the actual temperature<br />

gets below the acceptable difference.<br />

Delay 11149<br />

Circuit Setting range Factory setting<br />

1 1 ... 99 m 10 m<br />

If an alarm condition from either 'Upper difference' or 'Lower difference' is<br />

present for a longer time than the set delay (in min.), the alarm function<br />

is activated.<br />

1 ... 99 m: The alarm function will be activated if the alarm<br />

condition remains after the set delay.<br />

Flow temp. °C<br />

Flow temp. °C<br />

Temp.<br />

Upper difference (set<br />

value)<br />

Desired flow temp.<br />

Time<br />

Lower difference (set<br />

value)<br />

Desired flow temp.<br />

Time<br />

Flow temp.<br />

Alarm limit<br />

92 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy<br />

Time<br />

Delay