<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

Adapt. time (adaptation time) 11037<br />

Circuit Setting range Factory setting<br />

1 OFF / 1 ... 50 s 25 s<br />

Controls how fast the return temperature adapts to the desired return<br />

temperature limit (I control).<br />

OFF: The control function is not influenced by the ‘Adapt.<br />

time’.<br />

1: The desired temperature is adapted quickly.<br />

50: The desired temperature is adapted slowly.<br />

Priority (priority for return temp. limitation) - <strong>A217</strong>.3 11085<br />

Circuit Setting range Factory setting<br />

1 OFF / ON OFF<br />

Choose whether the return temperature limitation should overrule the set<br />

min. flow temperature ‘Temp. min.’ .<br />

OFF: The min. flow temperature limit is not overruled.<br />

ON: The min. flow temperature limit is overruled.<br />

The adaptation function can correct the desired flow temperature<br />

with max. 8 K.<br />

<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 77