5.5 Application<br />
Circ. P priority - <strong>A217</strong>.1 / <strong>A217</strong>.2 / <strong>A317</strong>.1 / <strong>A317</strong>.2 11055<br />
Circuit Setting range Factory setting<br />
1 OFF / ON OFF<br />
Choose whether the DHW circulation pump should be ON during DHW<br />
heating.<br />
OFF: The DHW circulation pump is switched OFF during DHW<br />
heating.<br />
ON: The DHW circulation pump is not switched OFF during<br />
DHW heating.<br />
Cont. T control - <strong>A217</strong>.1 / <strong>A217</strong>.2 / <strong>A317</strong>.1 / <strong>A317</strong>.2 11054<br />
Circuit Setting range Factory setting<br />
1 OFF / ON OFF<br />
Depending on the DHW circulation pipe connection, the desired DHW<br />
heating / charging temperature can be lowered when the DHW heating<br />
procedure has elapsed.<br />
OFF: The desired temperature at S3 or S4 is lowered to 10 °C.<br />
Typically, the DHW is circulated through the DHW tank.<br />
ON: The desired temperature at S3 or S4 is lowered to<br />
the desired DHW temperature. Typically, the DHW<br />
is circulated through the heat exchanger in order to<br />
compensate for the heat loss in the DHW circulation<br />
pipe.<br />
DHW P post-run - <strong>A217</strong>.1 / <strong>A317</strong>.1 11041<br />
Circuit Setting range Factory setting<br />
1 0 ... 30 m 0 m<br />
Set the DHW heating / charging pump (P1) post-run time (minutes). The<br />
pump can continue to be switched ON after the DHW heating procedure in<br />
order to utilize the remaining heat in the heat exchanger / boiler.<br />
0 ... 30: Set the number of minutes for the post-run.<br />
DHW P post-run - <strong>A217</strong>.2 / <strong>A317</strong>.2 11041<br />
Circuit Setting range Factory setting<br />
1 0 ... 30 m 0 m<br />
Set the DHW heating pump (P1) post-run time (minutes). The DHW heating<br />
pump can continue to be switched ON after the DHW heating procedure in<br />
order to utilize the remaining heat in the heat exchanger / boiler.<br />
0 ... 30: Set the number of minutes for the post-run.<br />
When the 'Circ. P priority' is set to OFF, the schedule for the DHW<br />
circulation pump is overruled.<br />
86 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy