2.7 Check list<br />
Is the <strong>ECL</strong> <strong>Comfort</strong> controller ready for use?<br />
Make sure that the correct power supply is connected to terminals 9 (Live) and 10 (Neutral).<br />
Check that the required controlled components (actuator, pump etc.) are connected to the correct terminals.<br />
Check that all sensors / signals are connected to the correct terminals (see 'Electrical connections').<br />
Mount the controller and switch on the power.<br />
Is the <strong>ECL</strong> Application Key inserted (see 'Inserting the Application Key').<br />
Is the correct language chosen (see 'Language' in 'Common controller settings').<br />
Is the time & date set correctly (see 'Time & Date' in 'Common controller settings').<br />
Is the right application chosen (see 'Identifying the system type').<br />
Check that all settings in the controller (see 'Settings overview') are set or that the factory settings comply with your<br />
requirements.<br />
Choose manual operation (see 'Manual control'). Check that valves open and close, and that required controlled<br />
components (pump etc.) start and stop when operated manually.<br />
Check that the temperatures / signals shown in the display match the actual connected components.<br />
Having completed the manual operation check, choose controller mode (scheduled, comfort, saving or frost protection).<br />