<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
<strong>A217</strong>.3 example a<br />
Indirectly connected DHW heating system. DHW circulation through heat exchanger.<br />
When the circulation pump P1 is in comfort mode, the desired temperature at S3 can be controlled.<br />
The desired DHW temperature at S3 can be controlled according to ‘Schedule’.<br />
The DHW circulation pump is controlled by ‘Schedule circ. pump’.<br />
Special settings for type <strong>A217</strong>.2 / <strong>A317</strong>.2 example a:<br />
Navigation: ID no.: Recommended setting:<br />
(Disabling flow switch function) MENU \ Settings \ Control par.: ‘Open time’ 11094 OFF<br />