<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

Units, <strong>ECL</strong> Key A2xx 11115<br />

Circuit Setting range Factory setting<br />

1 See the list ml, l/h<br />

Choice of units for measured values. Choose a value in the range 1 ... 9999<br />

in ‘Pulse’.<br />

Units to the left: pulse value.<br />

Units to the right: actual and limitation values.<br />

The value from the flow meter is expressed as ml or l.<br />

The value from the heat meter is expressed as Wh, kWh, MWh or<br />

GWh.<br />

The values for the actual flow and the flow limitation are expressed<br />

as l/h or m³/h.<br />

The values for the actual power and the power limitation are<br />

expressed as kW, MW or GW.<br />

Units — <strong>ECL</strong> Key A3xx 11115<br />

Circuit Setting range Factory setting<br />

1 See the list l/h<br />

Choice of units for measured values.<br />

Flow values are expressed as l/h or m³/h<br />

Power values are expressed as kW, MW or GW.<br />

List for setting range of 'Units':<br />

ml, l/h<br />

l, l/h<br />

ml, m³/h<br />

l, m³/h<br />

Wh, kW<br />

kWh, kW<br />

kWh, MW<br />

MWh, MW<br />

MWh, GW<br />

GWh, GW<br />

Example 1:<br />

'Units' (11115): l, m³/h<br />

'Pulse' (11114): 10<br />

Each pulse represents 10 litres and the flow is expressed as cubic<br />

meters (m³) per hour.<br />

Example 2:<br />

'Units' (11115): kWh, kW (= kilo Watt hour, kilo Watt)<br />

'Pulse' (11114): 1<br />

Each pulse represents 1 kilo Watt hour and the power is<br />

expressed in kilo Watt.<br />

List for setting range of 'Units':<br />

l/h<br />

m³/h<br />

kW<br />

MW<br />

GW<br />

80 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy