<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

When ST1 is activated by a high temperature (the TR temperature), the<br />

motorized control valve is closed gradually. At a higher temperature<br />

(the ST temperature), the safety circuit in the motorized control valve<br />

closes the valve immediately.<br />

Wire cross section: 0.5 - 1.5 mm²<br />

Incorrect connection can damage the electronic outputs.<br />

Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.<br />

<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 33