<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
Day<br />
Circuit Setting range Factory setting<br />
1 Weekdays<br />
Select (mark) the day(s) of the week where the anti-bacteria function must<br />
be active.<br />
M = Monday<br />
T = Tuesday<br />
W = Wednesday<br />
T = Thursday<br />
F = Friday<br />
S = Saturday<br />
S = Sunday<br />
Start time<br />
Circuit Setting range Factory setting<br />
1 00:00 ... 23:30 00:00<br />
Set the start time for the anti-bacteria function.<br />
Duration<br />
Circuit Setting range Factory setting<br />
1 10 ... 600 m 120 m<br />
Set the duration (minutes) for the anti-bacteria function.<br />
Desired T<br />
Circuit Setting range Factory setting<br />
1 OFF / 10 ... 110 °C OFF<br />
Set the desired DHW temperature for the anti-bacteria function.<br />
OFF: The anti-bacteria function is not active.<br />
10 ... 110: Desired DHW temperature during the anti-bacteria<br />
function period.<br />
<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 91