<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
5.3 Flow / power limit<br />
Depending on controller type, the flow / power limit is based on<br />
different input types:<br />
<strong>ECL</strong> Key<br />
application<br />
<strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong><br />
controller<br />
<strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong><br />
controller<br />
A2xx Pulse signal Pulse signal<br />
A3xx Not possible M-bus signal<br />
A flow or energy meter can be connected to the <strong>ECL</strong> controller in<br />
order to limit the flow or consumed power. The signal from the<br />
flow or energy meter can be based on pulse or M-bus signal.<br />
When the flow / power gets higher than the set limit, the controller<br />
gradually reduces the desired DHW temperature to obtain an<br />
acceptable max. flow or power consumption.<br />
Actual (actual flow or power) 11110<br />
Circuit Setting range Factory setting<br />
1 Read-out only<br />
The value is the actual flow or power based on the signal from flow / energy<br />
meter.<br />
Limit (limitation value) 11111<br />
Circuit Setting range Factory setting<br />
Set the limitation value.<br />
1 0.0 ... 999.9 l/h 999.9 l/h<br />
Adapt. time (adaptation time) 11112<br />
Circuit Setting range Factory setting<br />
1 OFF / 1 ... 50 s OFF<br />
Controls how fast the flow / power limitation adapts to the desired<br />
limitation.<br />
OFF: The control function is not influenced by the ‘Adapt.<br />
time’.<br />
1: The desired temperature is adapted quickly.<br />
50: The desired temperature is adapted slowly.<br />
Filter constant 11113<br />
Circuit Setting range Factory setting<br />
1 1 ... 50 10<br />
The actual filter dampens the flow / power input data by the set factor.<br />
1: Minor dampening (low filter constant)<br />
50: Major dampening (high filter constant)<br />
Flow / power<br />
limitation Limit<br />
Desired flow<br />
temp.<br />
° C<br />
Time<br />
If the ‘Adapt. time’ is too low, there is a risk of unstable control.<br />
78 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy