5.3 Flow / power limit<br />

Depending on controller type, the flow / power limit is based on<br />

different input types:<br />

<strong>ECL</strong> Key<br />

application<br />

<strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong><br />

controller<br />

<strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong><br />

controller<br />

A2xx Pulse signal Pulse signal<br />

A3xx Not possible M-bus signal<br />

A flow or energy meter can be connected to the <strong>ECL</strong> controller in<br />

order to limit the flow or consumed power. The signal from the<br />

flow or energy meter can be based on pulse or M-bus signal.<br />

When the flow / power gets higher than the set limit, the controller<br />

gradually reduces the desired DHW temperature to obtain an<br />

acceptable max. flow or power consumption.<br />

Actual (actual flow or power) 11110<br />

Circuit Setting range Factory setting<br />

1 Read-out only<br />

The value is the actual flow or power based on the signal from flow / energy<br />

meter.<br />

Limit (limitation value) 11111<br />

Circuit Setting range Factory setting<br />

Set the limitation value.<br />

1 0.0 ... 999.9 l/h 999.9 l/h<br />

Adapt. time (adaptation time) 11112<br />

Circuit Setting range Factory setting<br />

1 OFF / 1 ... 50 s OFF<br />

Controls how fast the flow / power limitation adapts to the desired<br />

limitation.<br />

OFF: The control function is not influenced by the ‘Adapt.<br />

time’.<br />

1: The desired temperature is adapted quickly.<br />

50: The desired temperature is adapted slowly.<br />

Filter constant 11113<br />

Circuit Setting range Factory setting<br />

1 1 ... 50 10<br />

The actual filter dampens the flow / power input data by the set factor.<br />

1: Minor dampening (low filter constant)<br />

50: Major dampening (high filter constant)<br />

Flow / power<br />

limitation Limit<br />

Desired flow<br />

temp.<br />

° C<br />

Time<br />

If the ‘Adapt. time’ is too low, there is a risk of unstable control.<br />

78 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy