<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
Min. act. time (min. activation time gear motor) 11189<br />
Circuit Setting range Factory setting<br />
1 2 ... 50 3<br />
The min. pulse period of 20 ms (milliseconds ) for activation of the gear<br />
motor.<br />
Supply T (idle) - <strong>A217</strong>.3 11097<br />
Circuit Setting range Factory setting<br />
1 OFF / ON OFF<br />
The ‘supply T (idle)’ is the supply temperature when there is no DHW tapping<br />
/ DHW draw-off. When DHW tapping / DHW draw-off is not detected (the<br />
flow switch is deactivated), the temperature is maintained at a (typical)<br />
lower level (saving temperature). Choose which temperature sensor is to<br />
maintain the saving temperature.<br />
OFF: The saving temperature is maintained at the DHW flow<br />
temperature sensor (S3).<br />
ON: The saving temperature is maintained at the supply<br />
temperature sensor (S2).<br />
Tn (idle) - <strong>A217</strong>.3 11096<br />
Circuit Setting range Factory setting<br />
3 1 ... 999 s 120 s<br />
Integration time is a constant when no DHW tapping / DHW draw-off is<br />
detected (the flow switch is deactivated), for slowly control of the saving<br />
temperature at either S3 or S2 (see also the setting in 11097).<br />
Set a high integration time constant to obtain a slow control.<br />
Set a low integration time constant for a fast control.<br />
Open time - <strong>A217</strong>.3 11094<br />
Circuit Setting range Factory setting<br />
1 OFF / 0.1... 25.0 s OFF<br />
Commands the actuator to open the valve for the set period when a<br />
DHW tapping / DHW draw-off starts. The DHW tapping / DHW draw-off<br />
is detected by the activated flow switch (S8). The ‘open time’ function<br />
compensates for the delay before the flow temperature sensor measures a<br />
change in temperature.<br />
OFF: The flow switch function is disabled.<br />
0.1 .... 25.0 s: Commanded opening time.<br />
Setting example Value x 20 ms<br />
2 40 ms<br />
10 200 ms<br />
50 1000 ms<br />
The setting should be kept as high as acceptable to increase the<br />
lifetime of the actuator (gear motor).<br />
If the S2 temperature sensor is not connected, the idle supply<br />
temperature will be maintained at S3.<br />
The ‘supply T (idle)’ function is only active if a value is chosen in 11094.<br />
<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 83