<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
3.6 Manual control<br />
It is possible to manually control the installed components.<br />
Manual control can only be selected in favorite displays in which<br />
the symbols for the controlled components (valve, pump etc.) are<br />
visible.<br />
Action: Purpose: Examples:<br />
Choose mode selector<br />
Confirm<br />
Choose manual mode<br />
Confirm<br />
Choose pump<br />
Confirm<br />
Switch ON the pump<br />
Switch OFF the pump.<br />
Confirm pump mode<br />
Choose motorized control valve<br />
Confirm<br />
Open the valve<br />
Stop opening the valve<br />
Close the valve<br />
Stop closing the valve<br />
Confirm valve mode<br />
To leave manual control, use the mode selector to select the<br />
desired mode. Push the dial.<br />
Manual control is typically used when commisioning the<br />
installation. The controlled components, valve, pump etc., can be<br />
controlled for correct function.<br />
Controlled components Circuit selector<br />
During manual operation, all control functions are deactivated. Frost<br />
protection is not active.<br />
When manual control is selected for one circuit, it is automatically<br />
selected for all circuits!<br />
Manual control of 0 - 10 volt controlled actuator:<br />
The actuator symbol has a value (in %) which can be changed. The %<br />
value is corresponding to a voltage value in the range 0 - 10 volt.<br />