<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

M exercise (valve exercise) - <strong>A217</strong>.3 11023<br />

Circuit Setting range Factory setting<br />

1 OFF / ON OFF<br />

Exercises the valve to avoid blocking in periods without DHW heating<br />

demand.<br />

OFF: The valve exercise is not active.<br />

ON: The valve opens for 7 minutes and closes for 7 minutes<br />

every third day at noon (12:00 hours).<br />

P post-run - A.217.3 11040<br />

Circuit Setting range Factory setting<br />

1 0 ... 99 m 3 m<br />

The circulation pump in the heating circuit can be ON for a number of<br />

minutes (m) after DHW heating stop .<br />

This function can utilize the remaining heat in e.g. a heat exchanger.<br />

0: The circulation pump stops immediately after the DHW<br />

heating stop.<br />

1 ... 99: The circulation pump is ON for the set time after the<br />

DHW heating stop.<br />

Ext. input (external override), <strong>ECL</strong> <strong>210</strong> 11141<br />

Circuit Setting range Factory setting<br />

1 OFF / S1 ... S8 OFF<br />

Choose the input for 'Ext. input' (external override). By means of a switch the<br />

controller can be overridden to <strong>Comfort</strong> or Saving mode.<br />

OFF: No inputs have been selected for external override.<br />

S1 ... S8: Input selected for external override.<br />

If S1...S6 is chosen as override input, the override switch must have<br />

gold-plated contacts.<br />

If S7 or S8 is chosen as override input, the override switch can be a<br />

standard contact.<br />

See the drawing for a connection example of an override switch<br />

to input S8.<br />

Choose only an unused input for override. If an already used input is<br />

applied for override, the functionality of this input is also neglected.<br />

See also ‘Ext. mode’.<br />

88 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy