<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

Ext. input (external override) — <strong>ECL</strong> <strong>310</strong> 11141<br />

Circuit Setting range Factory setting<br />

1 OFF / S1 ... S10 OFF<br />

Choose the input for 'Ext. input' (external override). By means of a switch the<br />

controller can be overridden to ‘<strong>Comfort</strong>’ or ‘Saving’ mode.<br />

OFF: No inputs have been selected for external override.<br />

S1 ... S10: Input selected for external override.<br />

If S1... S6 is chosen as override input, the override switch must have<br />

gold-plated contacts.<br />

If S7 ... S10 is chosen as override input, the override switch can be a<br />

standard contact.<br />

See the drawing for a connection example of an override switch<br />

to input S9.<br />

The two drawings (override to comfort mode and override to<br />

saving mode) show the functionality.<br />

Ext. mode (external override mode) 11142<br />

Circuit Setting range Factory setting<br />

1 COMFORT / SAVING COMFORT<br />

Choose external override mode.<br />

The mode override can be activated for saving or comfort mode.<br />

For override, the controller mode must be scheduled mode.<br />

SAVING: The controller is in saving mode when the override<br />

switch is closed.<br />

COMFORT: The controller is in comfort mode when the override<br />

switch is closed.<br />

Choose only an unused input for override. If an already used input is<br />

applied for override, the functionality of this input is also neglected.<br />

See also ‘Ext. mode’.<br />

Override to ‘<strong>Comfort</strong>’ mode<br />

Override to ‘Saving’ mode<br />

Time<br />

Time<br />

The result of override to 'Saving' mode depends on the setting in<br />

'Total stop'.<br />

Total stop = OFF: Heating reduced<br />

Total stop = ON: Heating stopped<br />

See also ‘Ext. input’.<br />

<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 89