<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
Max. charge T - <strong>A217</strong>.1 / <strong>A217</strong>.2 / <strong>A317</strong>.1 / <strong>A317</strong>.2 11152<br />
Circuit Setting range Factory setting<br />
1 10 ... 110 °C 80 °C<br />
Set the max. temperature at S3 for heating the DHW.<br />
10 ... 110: Set the temperature.<br />
Flow T adapt time - <strong>A217</strong>.2 / <strong>A317</strong>.2 11068<br />
Circuit Setting range Factory setting<br />
1 OFF / 1 ... 50 s 20 s<br />
Set the adaptation time (seconds) for the desired temperature at S3 based<br />
on the desired charging temperature at S4.<br />
The <strong>ECL</strong> <strong>Comfort</strong> controller gradually increases the desired temperature at<br />
S3 in order to maintain the desired temperature at S4.<br />
OFF: The desired flow temperature at S3 is not adapted to the<br />
desired charging temperature at S4.<br />
1: The adaptation is quick.<br />
50: The adaptation is slow.<br />
Temp. max. (flow temp. limit, max.) 11178<br />
Circuit Setting range Factory setting<br />
1 10 ... 150 °C 90 °C<br />
Set the max. flow temperature for the system. The desired flow<br />
temperature will not be higher than this setting. Adjust the factory<br />
setting, if required.<br />
Temp. min. (flow temp. limit, min.) 11177<br />
Circuit Setting range Factory setting<br />
1 10 ... 150 °C 10 °C<br />
Set the min. flow temperature for the system. The desired flow<br />
temperature will not be lower than this setting. Adjust the factory<br />
setting, if required.<br />
Charging principle<br />
S2 S3<br />
M1<br />
S5<br />
P1<br />
S4<br />
B<br />
P2<br />
The desired flow temperature at S3 cannot be higher than the set<br />
temperature in 'Max. charge T’.<br />
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />
‘Temp. min.’ can be overruled by the influence from the return<br />
temperature limitation (see 'Priority').<br />
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />
<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 75<br />
S6<br />
A<br />
S8<br />
P3<br />
<strong>Danfoss</strong><br />
87H2090.10