<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

Application <strong>A317</strong>.2<br />

<strong>ECL</strong> <strong>310</strong> / 230 V a.c.<br />

Terminal Description Max. load<br />

19 Phase for alarm output<br />

18 A1 Alarm 4 (2) A / 230 V a.c.*<br />

17 Not to be used<br />

16 Interconnection for phase<br />

15 Not to be used<br />

14 Phase for control of pumps<br />

13 P3 DHW circulation pump ON / OFF 4 (2) A / 230 V a.c.*<br />

12 P2 DHW charging pump ON / OFF 4 (2) A / 230 V a.c.*<br />

11 P1 DHW heating pump ON / OFF 4 (2) A / 230 V a.c.*<br />

10 Supply voltage 230 V a.c. - neutral (N)<br />

9 Supply voltage 230 V a.c. - live (L)<br />

8 M1 Phase for motorized control valve output<br />

7 M1 Motorized control valve - opening 0.2 A / 230 V a.c.<br />

6 M1 Motorized control valve - closing 0.2 A / 230 V a.c.<br />

5 Not to be used<br />

4 Not to be used<br />

3 Not to be used<br />

2 Not to be used<br />

1 Not to be used<br />

* Relay contacts: 4 A for ohmic load, 2 A for inductive load<br />

Factory established jumpers:<br />

5 to 8, 9 to 14, 14 to 16, 16 to 19, L to 5 and L to 9, N to 10<br />

<strong>Danfoss</strong><br />

87H2083.10<br />

Wire cross section: 0.5 - 1.5 mm²<br />

Incorrect connection can damage the electronic outputs.<br />

Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.<br />

<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 31