<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
5.0 Settings, circuit 1<br />
5.1 Tank temperature<br />
Charge difference - <strong>A217</strong>.1 / <strong>A217</strong>.2 / <strong>A317</strong>.1 / <strong>A317</strong>.2 11193<br />
Circuit Setting range Factory setting<br />
1 1 ... 50 K 15 K<br />
Set the number of degrees above the desired DHW temperature that will<br />
result in the DHW heating (charging) temperature.<br />
1... 50: Number of degrees to be added to the desired DHW<br />
temperature to obtain the DHW heating (charging)<br />
temperature.<br />
Start difference - <strong>A217</strong>.1 / <strong>A217</strong>.2 / <strong>A317</strong>.1 / <strong>A317</strong>.2 11195<br />
Circuit Setting range Factory setting<br />
1 –50 ... –1 K –3 K<br />
Set the number of degrees below the desired DHW temperature that will<br />
start the DHW heating (charging).<br />
-50 ... –1: Set the number of degrees.<br />
Temp.<br />
° C<br />
DHW heating<br />
Charge difference<br />
Stop difference<br />
Des. DHW temp.<br />
Start difference<br />
Actual DHW temp.<br />
Time<br />
The desired DHW temperature is related to the tank temperature<br />
sensor.<br />
If two tank temperature sensors are installed, the relation is to the<br />
upper tank temperature sensor.<br />
Example:<br />
Desired DHW temp.: 55 °C<br />
Start difference: -3 K<br />
Result:<br />
The DHW heating starts when the temperature measured by the tank<br />
temperature sensor (upper) is lower than 52 °C.<br />
Temp.<br />
° C<br />
DHW heating<br />
Start difference<br />
Desired DHW temp.<br />
DHW temp.<br />
<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 73<br />
Time