<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
Application <strong>A317</strong>.1<br />
<strong>ECL</strong> <strong>310</strong> / 24 V a.c.<br />
Terminal Description Max. load<br />
19 Phase for alarm output<br />
18 A1 Alarm 4 (2) A / 24 V a.c.*<br />
17 Not to be used<br />
16 Interconnection for phase<br />
15 Not to be used<br />
14 Phase for control of pumps<br />
13 K3 DHW circulation pump ON / OFF 4 (2) A / 24 V a.c.*<br />
12 Not to be used<br />
11 K1 DHW heating / charging pump ON / OFF 4 (2) A / 24 V a.c.*<br />
10 Supply voltage 24 V a.c. - (N)<br />
9 Supply voltage 24 V a.c. - (L)<br />
8 M1 Phase for motorized control valve output<br />
7 M1 Motorized control valve - opening 1 A / 24 V a.c.<br />
6 M1 Motorized control valve - closing 1 A / 24 V a.c.<br />
5 Not to be used<br />
4 Not to be used<br />
3 Not to be used<br />
2 Not to be used<br />
1 Not to be used<br />
* Relay contacts: 4 A for ohmic load, 2 A for inductive load<br />
Factory established jumpers:<br />
5 to 8, 9 to 14, 14 to 16, 16 to 19, L to 5 and L to 9, N to 10<br />
Wire cross section: 0.5 - 1.5 mm²<br />
Incorrect connection can damage the electronic outputs.<br />
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.<br />
40 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy<br />