<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Setting ID Page Factory settings in circuit(s)<br />

1 2 3<br />

P heat T (heat demand) 12078 141 20 °C<br />

P post-run 12040 141 3 m<br />

Frost pr. T (frost protection temperature) 12093 142 10 °C<br />

Ext. input (external override), <strong>ECL</strong> <strong>210</strong> 12141 142 OFF<br />

Ext. input (external override) — <strong>ECL</strong> <strong>310</strong> 12141 143 OFF<br />

Ext. mode (external override mode) 12142 143<br />

COM-<br />

FORT<br />

Day 144<br />

Start time 145 00:00<br />

Duration 145 120 m<br />

Desired T 145 OFF<br />

Upper difference 12147 146 OFF<br />

Lower difference 12148 146 OFF<br />

Delay 12149 147 10 m<br />

Lowest temp. 12150 147 30 °C<br />

Charge difference 13193 148 15 K<br />

Start difference 13195 148 –3 K<br />

Stop difference 13194 149 3 K<br />

Ch.-o. valve / P (changeover valve / pump) 13051 150 ON<br />

Tank, sec. / prim. 13053 150 OFF<br />

DHW P post-run 13041 150 0 m<br />

Send desired T 13500 150 ON<br />

Frost pr. T (frost protection temperature) 13093 150 10 °C<br />

Ext. input (external override), <strong>ECL</strong> <strong>210</strong> 13141 151 OFF<br />

Ext. input (external override) — <strong>ECL</strong> <strong>310</strong> 13141 151 OFF<br />

Ext. mode (external override mode) 13142 152<br />

COM-<br />

FORT<br />

Day 153<br />

Start time 154 00:00<br />

Duration 154 120 m<br />

Desired T 154 OFF<br />

Backlight (display brightness) 60058 164 5<br />

Contrast (display contrast) 60059 164 3<br />

Modbus addr. 38 165 1<br />

<strong>ECL</strong> 485 addr. (master / slave address) 2048 165 15<br />

Service Pin 2150 165 0<br />

Ext. reset 2151 166 0<br />

Language 2050 166 English<br />

102 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy