<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.<br />

120<br />

110<br />

100<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

1.8<br />

1.4<br />

1.0<br />

0.6<br />

0.2<br />

2.2 2.6 3.0 3.4<br />

-30 -20 -10<br />

0 10 20<br />

The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.<br />

Temp. max. (flow temp. limit, max.) 12178<br />

Circuit Setting range Factory setting<br />

2 10 ... 150 °C 45 °C<br />

Choose the allowed max. flow temperature for your system.<br />

Adjust the factory setting, if required.<br />

Temp. min. (flow temp. limit, min.) 12177<br />

Circuit Setting range Factory setting<br />

2 10 ... 150 °C 10 °C<br />

Choose the allowed min. flow temperature for your system.<br />

Adjust the factory setting, if required.<br />

The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />

The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />

124 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy