ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
<strong>A275</strong>.3, example f<br />
Boiler ON / OFF control, a mixing circuit control and a DHW circuit control. Optional DHW priority.<br />
* = pressure relief valve<br />
S1<br />
B1<br />
S3<br />
S5<br />
M2<br />
P3<br />
<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />
S4<br />
S2<br />
At DHW heating P3 is switched ON and the desired boiler temperature lies a number of degrees above the desired DHW temperature.<br />
Heating circuit 2 can be closed during DHW heating.<br />
Special settings for type <strong>A275</strong>.3, example f:<br />
Navigation: ID no.: Recommended setting:<br />
Boiler circuit (circuit 1)<br />
Circuit 1 must be able to receive a heat demand (desired flow temperature) from circuit 2:<br />
MENU \ Settings \ Application: 'Demand offset' 11017 3 K**<br />
** This value is added to the heat demand value from circuit 2<br />
Heating circuit (circuit 2)<br />
Circuit 2 must be able to send a heat demand (desired flow temperature) to circuit 1:<br />
MENU \ Settings \ Application: 'Send desired T' 12500 ON<br />
Circuit 2 can be closed during the DHW heating process:<br />
MENU \ Settings \ Application: ‘DHW priority' 12052 ***<br />
*** Set 'OFF' when not to be closed, set 'ON' when to be closed<br />
DHW circuit (circuit 3)<br />
DHW heating is managed by pump P3:<br />
MENU \ Settings \ Application: 'Ch.-o. valve / P' 13051 ON<br />
The desired DHW heating temperature must influence the boiler temperature:<br />
MENU \ Settings \ Application: ‘Tank, sec./prim.' 13053 OFF<br />
30 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />
P4<br />
S6<br />
S8<br />
②<br />
③<br />
<strong>Danfoss</strong><br />
87H2174.10