<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

<strong>A275</strong>.2, example a<br />

Boiler ON / OFF control for a heating and a DHW circuit. Optional DHW priority.<br />

* = pressure relief valve<br />

S1<br />

B1<br />

S3<br />

S5<br />

P1<br />

P3<br />

<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />

*<br />

At DHW heating P3 is switched ON and the desired boiler temperature lies a number of degrees above the desired DHW temperature.<br />

P1 is switched OFF.<br />

Special settings for type <strong>A275</strong>.2, example a:<br />

Navigation: ID no.: Recommended setting:<br />

DHW circuit (circuit 2)<br />

DHW heating is managed by pump P3:<br />

MENU \ Settings \ Application: 'Ch.-o. valve / P' 12051 ON<br />

The desired DHW heating temperature must influence the desired boiler temperature:<br />

MENU \ Settings \ Application: ‘Tank, sec./prim.' 12053 OFF<br />

Please note:<br />

If 'Ch.-o. valve / P' in 12051 is set to OFF, P3 will be switched on at DHW heating. The desired boiler temperature will still lie a<br />

number of degrees above the desired DHW temperature and P1 will remain switched ON.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 21<br />

A1<br />

S6<br />

S7<br />

①<br />

②<br />

<strong>Danfoss</strong><br />

87H2165.10