7.2 Application<br />

Ch.-o. valve / P (changeover valve / pump) 13051<br />

Circuit Setting range Factory setting<br />

3 OFF / ON ON<br />

Choose whether the DHW heating control is based on a changeover valve<br />

or a pump.<br />

OFF: Changeover valve<br />

ON: Pump<br />

Tank, sec. / prim. 13053<br />

Circuit Setting range Factory setting<br />

3 OFF / ON OFF<br />

Choose whether the heating of the DHW tank is dependent on the flow<br />

temperature at S3.<br />

OFF: The DHW tank is heated by means of the S3 temperature.<br />

ON: The DHW tank is heated separately. The S3 temperature<br />

has no influence on the DHW heating.<br />

DHW P post-run 13041<br />

Circuit Setting range Factory setting<br />

3 0 ... 30 m 0 m<br />

Set the DHW pump (P3) post-run time (minutes). The DHW pump can<br />

continue to be switched ON after the DHW heating procedure in order to<br />

utilize the remaining heat in the heat exchanger / boiler.<br />

0 ... 30: Set the number of minutes for the post-run.<br />

Send desired T 13500<br />

Circuit Setting range Factory setting<br />

3 OFF / ON ON<br />

When the controller acts as a slave controller in a master / slave system,<br />

information about the desired flow temperature can be sent to the master<br />

controller via the <strong>ECL</strong> 485 bus.<br />

OFF: Information about the desired flow temperature is not<br />

sent to the master controller.<br />

ON: Information about the desired flow temperature is sent<br />

to the master controller.<br />

Frost pr. T (frost protection temperature) 13093<br />

Circuit Setting range Factory setting<br />

3 5 ... 40 °C 10 °C<br />

Set the desired flow temperature to protect the DHW system against frost.<br />

5 ... 40: Desired frost protection temperature.<br />

When the changeover valve is chosen, pump P1 is ON at heating as<br />

well as at DHW heating demand.<br />

When the pump is chosen, pump P1 is ON at heating and OFF at DHW<br />

heating demand.<br />

In the master controller, 'Demand offset' must be set to a value in order<br />

to react on a desired flow temperature from a slave controller.<br />

150 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy