<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
<strong>A375</strong>.1, example d<br />
2 x boiler ON / OFF control for a heating circuit. The boiler circuit is equipped with a low loss header.<br />
S1<br />
* = pressure relief valve<br />
B1 B2<br />
S3<br />
S5<br />
The pumps in the boiler are not controlled.<br />
Rotating sequence: Burner 1 is active before burner 2. Next day burner 2 is active before burner 1.<br />
One burner step is active at low heat demand. At increased heat demand the next burner step is activated additionally<br />
The last burner step can be disabled if the outdoor temperature is higher than a set value.<br />
Special settings for type <strong>A375</strong>.1, example d:<br />
<strong>ECL</strong> <strong>310</strong><br />
P1<br />
Navigation: ID no.: Recommended setting:<br />
Heating circuit (circuit 1)<br />
Sequence type (code) for controlling the burners:<br />
MENU \ Settings \ Boiler: 'Sequence type' 11072 0<br />
Number of total burner steps:<br />
MENU \ Settings \ Boiler: ‘Steps' 11073 2<br />
<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 35<br />