<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

<strong>A275</strong>.3, example b<br />

Boiler ON / OFF control for a direct heating circuit (1), a mixing circuit (2) and a DHW circuit (3). Partly DHW priority.<br />

* = pressure relief valve<br />

S1<br />

B1<br />

S3<br />

S5<br />

P1<br />

P3/M1<br />

M2<br />

<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />

S4<br />

S2<br />

Heating circuit 2 can alternatively be a floor heating circuit.<br />

At DHW heating P3 (changeover valve) is activated and the desired boiler temperature is a number of degrees above the desired DHW<br />

temperature.<br />

P1 is continuously switched ON.<br />

Heating circuit 2 can be closed during DHW heating.<br />

Special settings for type <strong>A275</strong>.3, example b:<br />

P4<br />

*<br />

Navigation: ID no.: Recommended setting:<br />

Heating circuit (circuit 1)<br />

Circuit 1 must be able to receive a heat demand (desired flow temperature) from circuit 2:<br />

MENU \ Settings \ Application: 'Demand offset' 11017 3 K**<br />

** This value is added to the heat demand value from circuit 2<br />

Heating circuit (circuit 2)<br />

Circuit 2 must be able to send a heat demand (desired flow temperature) to circuit 1:<br />

MENU \ Settings \ Application: 'Send desired T' 12500 ON<br />

Circuit 2 can be closed during the DHW heating process:<br />

MENU \ Settings \ Application: ‘DHW priority' 12052 ***<br />

*** Set 'OFF' when not to be closed, set 'ON' when to be closed<br />

DHW circuit (circuit 3)<br />

DHW heating is managed by changeover valve P3 / M1:<br />

MENU \ Settings \ Application: 'Ch.-o. valve / P' 13051 OFF<br />

The desired DHW heating temperature must influence the boiler temperature:<br />

MENU \ Settings \ Application: ‘Tank, sec./prim.' 13053 OFF<br />

26 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />