<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

2.5.6 Electrical connections, ECA 30 / 31<br />

Terminal<br />

<strong>ECL</strong><br />

Terminal<br />

ECA 30 / 31<br />

30 4<br />

31 1<br />

32 2<br />

33 3<br />

4<br />

5<br />

Description Type<br />

(recomm.)<br />

Twisted pair<br />

Twisted pair<br />

Ext. room temperature<br />

sensor*<br />

Cable 2 x<br />

twisted pair<br />

ESM-10<br />

* After an external room temperature sensor has been connected,<br />

ECA 30 / 31 must be repowered.<br />

The communication to the ECA 30 / 31 must be set up in the <strong>ECL</strong><br />

<strong>Comfort</strong> controller in 'ECA addr.'<br />

The ECA 30 /31 must be set up accordingly.<br />

After application setup the ECA 30 / 31 is ready after 2–5 min. A<br />

progress bar in the ECA 30 / 31 is displayed.<br />

ECA 30 / 31<br />

ESM-10<br />

<strong>ECL</strong> <strong>210</strong> / <strong>310</strong><br />

ECA information message:<br />

‘Application req. newer ECA’:<br />

The software of your ECA does not comply with the software of your<br />

<strong>ECL</strong> <strong>Comfort</strong> controller. Please contact your <strong>Danfoss</strong> sales office.<br />

Total cable length: Max. 200 m (all sensors incl. internal <strong>ECL</strong> 485<br />

communication bus).<br />

Cable lengths of more than 200 m may cause noise sensibility (EMC).<br />

Max. two ECA 30 / 31 can be connected to an <strong>ECL</strong> <strong>Comfort</strong> controller<br />

or to master / slave systems with several <strong>ECL</strong> <strong>Comfort</strong> controllers.<br />

Total cable length: Max. 200 m (all sensors incl. internal <strong>ECL</strong> 485<br />

communication bus).<br />

Cable lengths of more than 200 m may cause noise sensibility (EMC).<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 73<br />

B<br />

A<br />

B<br />

A<br />

<strong>Danfoss</strong><br />

87H2051.10