<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

2.5.7 Electrical connections, master / slave systems<br />

The controller can be used as master or slave in master / slave<br />

systems via the internal <strong>ECL</strong> 485 communication bus (2 x twisted<br />

pair cable).<br />

The <strong>ECL</strong> 485 communication bus is not compatible with the <strong>ECL</strong><br />

bus in <strong>ECL</strong> <strong>Comfort</strong> 110, 200, 300 and 301!<br />

Terminal Description Type<br />

(recomm.)<br />

30 Common terminal<br />

31* +12 V*, <strong>ECL</strong> 485 communication bus<br />

32 B, <strong>ECL</strong> 485 communication bus<br />

33 A, <strong>ECL</strong> 485 communication bus<br />

Cable 2 x<br />

twisted pair<br />

* Only for ECA 30 / 31 and master / slave communication<br />

B<br />

A<br />

B<br />

A<br />

Total cable length: Max. 200 m (all sensors incl. internal <strong>ECL</strong> 485<br />

communication bus).<br />

Cable lengths of more than 200 m may cause noise sensibility (EMC).<br />

74 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />

B<br />

A<br />

B<br />

A<br />

<strong>Danfoss</strong><br />

87H2052.10