<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

2.5.2 Electrical connections, 230 V a.c., power supply, pumps, motorized control valves etc.<br />

Application <strong>A275</strong>.1 / <strong>A275</strong>.2<br />

Terminal Description Max. load<br />

16<br />

15<br />

Alarm (A1) 4 (2) A / 230 V a.c.*<br />

14 Phase for pumps and burner<br />

13 P3 DHW heating pump ON / OFF, circuit 2 (<strong>A275</strong>.2 only) 4 (2) A / 230 V a.c.*<br />

12 B1 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />

11 P1 Circulation pump ON / OFF, circuit 1 4 (2) A / 230 V a.c.*<br />

10 Supply voltage 230 V a.c. - neutral (N)<br />

9 Supply voltage 230 V a.c. - live (L)<br />

8 M1 Phase for motorized changeover valve output, circuit 2 (<strong>A275</strong>.2 only)<br />

7 M1 Motorized changeover valve, DHW circuit direction (<strong>A275</strong>.2 only) 0.2 A / 230 V a.c.<br />

6 M1 Motorized changeover valve, heating circuit direction, (<strong>A275</strong>.2 only) 0.2 A / 230 V a.c.<br />

* Relay contacts: 4 A for ohmic load, 2 A for inductive load<br />

Factory established jumpers:<br />

5 to 8, 9 to 14 , L to 5 and L to 9, N to 10<br />