02.08.2013 Views

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Infl. - min. (room temp. limitation, min.) 12183<br />

Circuit Setting range Factory setting<br />

2 0.0 .... 9.9 0.0<br />

Determines how much the desired flow temperature will be influenced<br />

(increased) if the actual room temperature is lower than the desired room<br />

temperature (P control).<br />

0.0: The room temperature has no influence.<br />

9.9: The room temperature has a big influence.<br />

Adapt. time (adaption time) 12015<br />

Circuit Setting range Factory setting<br />

2 OFF / 1 ... 50 s OFF<br />

Controls how fast the actual room temperature adapts to the desired room<br />

temperature (I control).<br />

OFF: The control function is not influenced by the 'Adapt.<br />

time'.<br />

1: The desired room temperature is adapted quickly.<br />

50: The desired room temperature is adapted slowly.<br />

The adaptation function can correct the desired flow temperature<br />

with max. 8 K x heat curve value.<br />

128 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!