<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

2.5.5 Electrical connections, Pt 1000 temperature sensors and signals<br />

<strong>A275</strong>:<br />

Terminal Sensor / description Type<br />

(recomm.)<br />

29 and 30 S1 Outdoor temperature sensor* ESMT<br />

28 and 30 S2 <strong>A275</strong>.3 only:<br />

Return temperature sensor,<br />

circuit 2<br />

27 and 30 S3 Boiler temperature sensor**,<br />

circuit 1<br />

26 and 30 S4 <strong>A275</strong>.3 only:<br />

Flow temperature sensor**,<br />

circuit 2<br />

25 and 30 S5 Return temperature sensor,<br />

circuit 1<br />

24 and 30 S6 <strong>A275</strong>.2 / <strong>A275</strong>.3 only:<br />

DHW tank temperature sensor,<br />

circuit 2 / 3<br />

23 and 30 S7 Room temperature sensor***,<br />

circuit 1<br />

22 and 30 S8 <strong>A275</strong>.3 only:<br />

Room temperature sensor***,<br />

circuit 2<br />

ESM-11 / ESMB /<br />

ESMC / ESMU<br />

ESMU / ESMB<br />

ESM-11 / ESMB /<br />

ESMC / ESMU<br />

ESM-11 / ESMB /<br />

ESMC / ESMU<br />

ESM-11 / ESMB /<br />

ESMC / ESMU<br />

ESM-10<br />

ESM-10<br />

* If the outdoor temperature sensor is not connected or the<br />

cable is short-circuited, the controller assumes that the<br />

outdoor temperature is 0 (zero) °C.<br />

** The boiler / flow temperature sensor must always be<br />

connected in order to have the desired functionality. If the<br />

sensor is not connected or the cable is short-circuited, the<br />

motorized control valve closes (safety function).<br />

*** Only for room temperature sensor connection. The room<br />

temperature signal can also be available from a Remote<br />

Control Unit (ECA 30 / 31). See 'Electrical connections, ECA<br />

30 / 31'.<br />

Factory established jumper:<br />

30 to common terminal.<br />

70 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy