<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

<strong>A375</strong> APPLICATIONS:<br />

<strong>A375</strong>.1, example a<br />

One boiler with 2 x burner ON / OFF control for a heating circuit.<br />

* = pressure relief valve<br />

S1<br />

B2<br />

B1<br />

S3<br />

S5<br />

P1<br />

<strong>ECL</strong> <strong>310</strong><br />

Fixed sequence: Burner 1 must be switched ON before burner 2 can be switched ON.<br />

Burner 1 is active at low heat demand. At increased heat demand burner 2 is activated additionally.<br />

The last burner step can be disabled if the outdoor temperaure is higher than a set value.<br />

Special settings for type <strong>A375</strong>.1, example a:<br />

*<br />

Navigation: ID no.: Recommended setting:<br />

Heating circuit (circuit 1)<br />

Sequence type (code) for controlling the burners:<br />

MENU \ Settings \ Boiler: 'Sequence type' 11072 3<br />

Number of total burner steps:<br />

MENU \ Settings \ Boiler: ‘Steps' 11073 2<br />

32 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />