Pre-stop (optimized stop time) 12026<br />

Circuit Setting range Factory setting<br />

2 OFF / ON ON<br />

Disable the optimized stop time.<br />

OFF: The optimized stop time is disabled.<br />

ON: The optimized stop time is enabled.<br />

Based on (optimization based on room / outdoor temp.) 12020<br />

Circuit Setting range Factory setting<br />

2 OUT / ROOM OUT<br />

The optimized start and stop time can be based on either room or outdoor<br />

temperature.<br />

OUT: Optimization based on outdoor temperature. Use this<br />

setting if the room temperature is not measured.<br />

ROOM: Optimization based on room temperature, if measured.<br />

Total stop 12021<br />

Circuit Setting range Factory setting<br />

2 OFF / ON OFF<br />

Decide whether you want a total stop during the saving temperature period.<br />

OFF: No total stop. The desired flow temperature is reduced<br />

according to:<br />

• desired room temperature in saving mode<br />

• auto saving<br />

ON: The desired flow temperature is lowered to the set value<br />

in ‘Frost pr.’ The circulation pump is stopped but frost<br />

protection is still active, see 'P frost T'.<br />

Example: Optimization of <strong>Comfort</strong> from 07:00 - 22:00<br />

07:00 22:00<br />

Optimization start Optimization stop<br />

Desired flow temp. °C<br />

Desired flow temp. °C<br />

Schedule<br />

Pre-stop OFF<br />

Pre-stop ON<br />

Total stop = ON<br />

‘Frost pr.’<br />

Time<br />

Total stop = OFF<br />

‘Frost pr.’<br />

Time<br />

The min. flow temperature limitation ('Temp. min.') is overruled when<br />

'Total stop' is ON.<br />

134 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy