02.08.2013 Views

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Ext. input (external override), <strong>ECL</strong> <strong>210</strong> 11141<br />

Circuit Setting range Factory setting<br />

1 OFF / S1 ... S8 OFF<br />

Choose the input for 'Ext. input' (external override). By means of a switch the<br />

controller can be overridden to <strong>Comfort</strong> or Saving mode.<br />

OFF: No inputs have been selected for external override.<br />

S1 ... S8: Input selected for external override.<br />

If S1...S6 is chosen as override input, the override switch must have<br />

gold-plated contacts.<br />

If S7 or S8 is chosen as override input, the override switch can be a<br />

standard contact.<br />

See the drawing for a connection example of an override switch<br />

to input S8.<br />

Choose only an unused input for override. If an already used input is<br />

applied for override, the functionality of this input is also neglected.<br />

See also ‘Ext. mode’.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 121

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!