<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Based on (optimization based on room / outdoor temp.) 11020<br />

Circuit Setting range Factory setting<br />

1 OUT / ROOM OUT<br />

The optimized start and stop time can be based on either room or outdoor<br />

temperature.<br />

OUT: Optimization based on outdoor temperature. Use this<br />

setting if the room temperature is not measured.<br />

ROOM: Optimization based on room temperature, if measured.<br />

Total stop 11021<br />

Circuit Setting range Factory setting<br />

1 OFF / ON OFF<br />

Decide whether you want a total stop during the saving temperature period.<br />

OFF: No total stop. The desired flow temperature is reduced<br />

according to:<br />

• desired room temperature in saving mode<br />

• auto saving<br />

ON: The desired flow temperature is lowered to the set value<br />

in ‘Frost pr.’ The circulation pump is stopped but frost<br />

protection is still active, see 'P frost T'.<br />

Cut-out (limit for heating cut-out) 11179<br />

Circuit Setting range Factory setting<br />

1 OFF / 1 ... 50 °C 20 °C<br />

The heating can be switched OFF when the outdoor temperature is<br />

higher than the set value. The valve closes and after the post-run<br />

time, the heating circulation pump stops. ‘Temp. min.’ will be<br />

overruled.<br />

The heating system switches ON again when the outdoor<br />

temperature and the accumulated (filtered) outdoor temperature<br />

become lower than the set limit.<br />

This function can save energy.<br />

Set the value for outdoor temperature at which you want the<br />

heating system to switch OFF.<br />

Desired flow temp. °C<br />

Desired flow temp. °C<br />

Total stop = ON<br />

‘Frost pr.’<br />

Time<br />

Total stop = OFF<br />

‘Frost pr.’<br />

Time<br />

The min. flow temperature limitation ('Temp. min.') is overruled when<br />

'Total stop' is ON.<br />

Temp. Actual outdoor temp. Accumulated outdoor temp.<br />

18 °C<br />

Heating ON Heating OFF Heating ON<br />

Time<br />

The heating cut-out is only active when the controller mode is in<br />

scheduled operation. When the cut-out value is set to OFF, there is<br />

no heating cut-out.<br />