<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
Application Key: Situation 3<br />
A copy of the controllers settings is needed for configuring<br />
another controller.<br />
This function is used<br />
• for saving (backup) of special user and system settings<br />
• when another <strong>ECL</strong> <strong>Comfort</strong> controller of the same type (<strong>210</strong> or<br />
<strong>310</strong>) must be configured with the same application but user /<br />
system settings differ from the factory settings.<br />
How to copy to another <strong>ECL</strong> <strong>Comfort</strong> controller:<br />
*<br />
Action: Purpose: Examples:<br />
Choose ‘MENU’<br />
Confirm<br />
Choose the circuit selector at the top<br />
right corner in the display<br />
Confirm<br />
Choose 'Common controller settings'<br />
Confirm<br />
Go to ‘Key functions’<br />
Confirm<br />
Choose ‘Copy’<br />
Confirm<br />
Choose ‘To’.<br />
‘<strong>ECL</strong>’ or ‘KEY’ will be indicated. Choose<br />
’<strong>ECL</strong>’ or KEY’<br />
Push the dial repeatedly to choose<br />
copy direction<br />
Choose ‘System settings’ or ‘User<br />
settings’<br />
Push the dial repeatedly to choose<br />
‘Yes’ or ‘No’ in ‘Copy’. Push to confirm.<br />
Choose ‘Start copying’<br />
The Application Key or the controller<br />
is updated with special system or user<br />
settings.<br />
*<br />
’<strong>ECL</strong>’ or ‘KEY’.<br />
**<br />
‘NO’ or ‘YES’<br />
‘<strong>ECL</strong>’: Data will be copied from the Application Key to the<br />
<strong>ECL</strong> Controller.<br />
‘KEY’: Data will be copied from the <strong>ECL</strong> Controller to the<br />
Application Key.<br />
**<br />
‘NO’: The settings from the <strong>ECL</strong> controller will not be copied<br />
to the Application Key or to the <strong>ECL</strong> <strong>Comfort</strong> controller.<br />
‘YES’: Special settings (differing from the factory settings) will<br />
be copied to the Application Key or to the <strong>ECL</strong> <strong>Comfort</strong><br />
controller. If YES can not be chosen, there are no special<br />
settings to be copied.<br />