02.08.2013 Views

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

<strong>A375</strong>.1, example f<br />

Up to 4 x boiler ON / OFF control for a heating circuit.<br />

S1<br />

* = pressure relief valve<br />

B1 B4<br />

S3<br />

S5<br />

Rotating sequence of the boilers: Boiler 1 - 2 - 3 - 4. Next day: Boiler 2 - 3 - 4 -1. Following day: Boiler 3 - 4 -1 - 2 and so on.<br />

Burner steps are activated according to heat demand.<br />

<strong>ECL</strong> <strong>310</strong><br />

The last burner step can be disabled if the outdoor temperaure is higher than a set value.<br />

Special settings for type <strong>A375</strong>.1, example f:<br />

P1<br />

Navigation: ID no.: Recommended setting:<br />

Heating circuit (circuit 1)<br />

Sequence type (code) for controlling the burners:<br />

MENU \ Settings \ Boiler: 'Sequence type' 11072 0<br />

Number of total burner steps:<br />

MENU \ Settings \ Boiler: ‘Steps' 11073 4<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 37<br />

A1<br />

*<br />

S7<br />

①<br />

<strong>Danfoss</strong><br />

87H2181.10

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!