02.08.2013 Views

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Ramp (reference ramping) 12013<br />

Circuit Setting range Factory setting<br />

2 OFF / 1 ... 99 m OFF<br />

The time (minutes) in which the desired flow temperature increases<br />

gradually to avoid load peaks in the heat supply.<br />

OFF: The ramping function is not active.<br />

1-99 m: The desired flow temperature is increased gradually with<br />

the set minutes.<br />

In order to avoid load peaks in the supply network, the flow<br />

temperature can be set to increase gradually after a period with<br />

saving temperature. This causes the valve to open gradually.<br />

Optimizer (optimizing time constant) 12014<br />

Circuit Setting range Factory setting<br />

2 OFF / 10 ... 59 OFF<br />

Optimizes the start and stop times for the comfort temperature period to<br />

obtain the best comfort at the lowest energy consumption.<br />

The lower the outdoor temperature, the earlier the heating cut-in. The lower<br />

the outdoor temperature, the later the heating cut-out.<br />

The optimized heating cut-out time can be automatic or disabled. The<br />

calculated start and stop times are based on the setting of the optimizing<br />

time constant.<br />

Adjust the optimizing time constant.<br />

The value consists of a two digit number. The two digits have the<br />

following meaning (digit 1 = Table I, digit 2 = Table II).<br />

OFF: No optimization. The heating starts and stops at the<br />

times set in the schedule.<br />

10 ... 59: See tables I and II.<br />

Table I:<br />

Temp. °C<br />

Ramping time<br />

Time (min.)<br />

Left digit Heat accumulation of the<br />

building<br />

1- light<br />

Table II:<br />

2- medium<br />

3- heavy<br />

4- medium<br />

5- heavy<br />

System type<br />

Radiator<br />

systems<br />

Floor heating<br />

systems<br />

Right digit Dimensioning temperature Capacity<br />

-0 -50 °C large<br />

-1 -45 °C ·<br />

· · ·<br />

-5 -25 °C normal<br />

· · ·<br />

-9 -5 °C small<br />

Dimensioning temperature:<br />

The lowest outdoor temperature (usually determined by your system<br />

designer in connection with the design of the heating system) at which<br />

the heating system can maintain the designed room temperature.<br />

Example<br />

The system type is radiator, and the heat accumulation of the building<br />

is medium.<br />

The left digit is 2.<br />

The dimensioning temperature is -25 °C, and the capacity is normal.<br />

The right digit is 5.<br />

Result:<br />

The setting is to be changed to 25.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 133

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!