<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

2.0 <strong>Installation</strong><br />

2.1 Before you start<br />

The application <strong>A275</strong>.1 is very flexible. These are the basic<br />

principles:<br />

Heating (circuit 1):<br />

Typically, the boiler temperature is adjusted according to your<br />

requirements. The boiler temperature sensor S3 is the most<br />

important sensor. It must be placed correctly in order to measure<br />

the boiler temperature. The desired boiler temperature at S3 is<br />

calculated in the <strong>ECL</strong> controller, based on the outdoor temperature<br />

(S1). The lower the outdoor temperature, the higher the desired<br />

boiler temperature. The boiler temperature is also the flow<br />

temperature in the direct connected heating circuit.<br />

By means of a week schedule (up to 3 ‘<strong>Comfort</strong>’ periods / day), the<br />

heating circuit can be in ‘<strong>Comfort</strong>’ or ‘Saving’ mode (two different<br />

temperature values for the desired room temperature). In 'Saving'<br />

mode a 'Total stop' function can be selected in order to switch OFF<br />

the heating.<br />

The burner is switched ON when the boiler temperature is<br />

lower than the desired boiler temperature and switched OFF<br />

when the boiler temperature is higher than the desired boiler<br />

temperature. A switching difference determines the ON / OFF<br />

control. Furthermore, the boiler protection function will only<br />

switch ON the circulation pump if the boiler temperature gets<br />

above a minimum temperature. A minimum ON-time can be set for<br />

the burner in order to increase the boiler's efficiency.<br />

The return temperature (S5) to the boiler should not be too<br />

high (condensing boiler) or too low (oil or gas fired boiler). If so,<br />

the desired boiler temperature can be decreased or increased.<br />

Furthermore, the return temperature limitation can be dependent<br />

of the outdoor temperature. Typically, the lower the outdoor<br />

temperature, the higher the accepted return temperature.<br />

If the measured room temperature (measured by S7 or the remote<br />

control unit ECA 30) does not equal the desired room temperature,<br />

the desired boiler temperature can be adjusted.<br />

The circulation pump (P1) is ON at heat demand or at frost<br />

protection.<br />

The heating can be switched OFF if the outdoor temperature gets<br />

higher than a set value.<br />

Typical <strong>A275</strong>.1 application:<br />

S1<br />

B1<br />

S3<br />

S5<br />

* Pressure relief valve<br />

P1<br />

<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />

*<br />

The shown diagram is a fundamental and simplified example and does<br />

not contain all components that are necessary in a system.<br />

All named components are connected to the <strong>ECL</strong> <strong>Comfort</strong> controller.<br />

List of components:<br />

S1 Outdoor temperature sensor<br />

S3 Boiler temperature sensor<br />

S5 Return temperature sensor<br />

S7 Room temperature sensor / ECA 30<br />

P1 Circulation pump<br />

B1 Burner<br />

A1 Alarm<br />

The controller is pre-programmed with factory settings that are shown<br />

in the relevant chapters of this guide.<br />