<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Sequence type (<strong>A375</strong> applications) 11072<br />

Circuit Setting range Factory setting<br />

1 0 ... 4 3<br />

Set the sequence type for the boiler system.<br />

Code:<br />

0<br />

1<br />

2<br />

3<br />

4<br />

Boilers in sequence with automatic changeover of main<br />

boiler.<br />

Boilers in sequence with 1 fixed main boiler and<br />

automatic changeover of additional boilers.<br />

Boilers in sequence with 2 fixed main boilers and<br />

automatic changeover of additional boilers.<br />

Boilers in fixed sequence.<br />

2-step boilers in sequence with automatic changeover<br />

of main boiler.<br />

Stop at T out 11038<br />

Circuit Setting range Factory setting<br />

1 –49 ... 49 °C / OFF OFF<br />

<strong>A275</strong> applications:<br />

If the outdoor temperature is higher than the set value, the burner will not<br />

be cut-in.<br />

<strong>A375</strong> applications:<br />

If the outdoor temperature is higher than the set value, the last burner step<br />

will not be cut-in.<br />

–49 ... 49: Set the value for blocking the last burner step.<br />

OFF: The 'Stop at T out' function is not active.<br />

<strong>Danfoss</strong><br />

87H2193.10<br />

I<br />

II<br />

III<br />

The changeover takes place after midnight. However, the changeover<br />

to the next main boiler is carried out at a natural cut-out of a boiler<br />

(see example).<br />

The symbol ‘ŋ’ in the sequence type examples indicates the number<br />

of burner steps in the system.<br />

<strong>A375</strong>.1:<br />

B1 — B4 are controlled by the <strong>ECL</strong> <strong>Comfort</strong> controller<br />

B5 — B8 are controlled by ECA 32<br />

<strong>A375</strong>.2 / <strong>A375</strong>.3:<br />

B1 — B2 are controlled by the <strong>ECL</strong> <strong>Comfort</strong> controller<br />

B3 — B6 are controlled by ECA 32<br />

B7 — B8 are controlled by the <strong>ECL</strong> <strong>Comfort</strong> controller<br />

The ‘Stop at T out’ can be used in connection with alternative heat<br />

supply sources such as heat pumps and solar systems.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 115