<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

7.3 Anti-bacteria<br />

On selected days during the week the DHW temperature can<br />

be increased in order to neutralize bacteria in the DHW system.<br />

The desired DHW temperature 'Desired T' (typically 80 °C) will be<br />

present for the selected day(s) and duration.<br />

The anti-bacteria function is not active in frost protection mode.<br />

Day<br />

Circuit Setting range Factory setting<br />

3 Weekdays<br />

Select (mark) the day(s) of the week where the anti-bacteria function must<br />

be active.<br />

M = Monday<br />

T = Tuesday<br />

W = Wednesday<br />

T = Thursday<br />

F = Friday<br />

S = Saturday<br />

S = Sunday<br />

Desired temp.<br />

80<br />

55<br />

° C<br />

Day / start time Duration<br />

Time<br />

During the anti-bacteria process, the return temperature limitation is<br />

not active.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 153