<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Protection 11047<br />

Circuit Setting range Factory setting<br />

1 OFF / ON OFF<br />

Choose whether the circulation pump for the boiler circuit (P1) should be<br />

stopped to prevent condensation in the boiler during the heating-up period.<br />

OFF: The circulation pump is controlled according to<br />

demand.<br />

The circulation pump is switched ON when:<br />

· the desired flow (boiler) temperature is higher<br />

than the set value in ID no. 11078 ‘P heat T’ or<br />

· the outdoor temperature is lower than the set<br />

value in ID no. 11077 ‘P frost T’.<br />

ON: The circulation pump is switched OFF until the desired<br />

min. flow (boiler) temperature is reached.<br />

The min. flow (boiler) temperature is set in ID no.<br />

11177 ‘Temp. min.’.<br />

Typically, the heating-up period of an oil fired boiler must be as short<br />

as possible. This will reduce condensation in the furnace.<br />

To obtain the best conditions for the boiler, the circulation pump (P1)<br />

can be switched OFF during the heating-up period.<br />

The circulation pump will be switched ON when the actual flow<br />

(boiler) temperature is higher than the min. desired flow (boiler)<br />

temperature set in ID no. 11177 ‘Temp. min.’ + half the boiler<br />

temperature difference in ID no. 11046 ‘Difference’.<br />

The circulation pump will be switched OFF again if the actual flow<br />

(boiler) temperature is lower than the min. desired flow (boiler)<br />

temperature set in ID no. 11177 ‘Temp. min.’.<br />

Example:<br />

‘Temp. min.’= 45 °C and ‘Difference’ = 8 K<br />

The circulation pump will be switched ON when the actual flow<br />

(boiler) temperature is higher than 45 + 0.5 x 8 = 49 °C.<br />

The circulation pump will be switched OFF when the flow (boiler)<br />

temperature gets lower than 45 °C.<br />

Band limit (<strong>A375</strong> applications) 11048<br />

Circuit Setting range Factory setting<br />

1 5 ... 80 K 20 K<br />

The band limit determines when burners are cut-in and cut-out if there is<br />

a temperature difference between the desired and the actual flow (boiler)<br />

temperature.<br />

If the difference is more than the set value, the setting in ID 11074 ‘Reaction,<br />

o. band’ determines the control of burner steps. If the difference is less than<br />

the set value, the setting in ID no. 11075 ‘Reaction in band’ determines the<br />

control of burner steps.<br />

5 ... 80 K: Set the band limit.<br />

Flow (boiler) temp.<br />

Temp.<br />

0.5 x ‘Difference’<br />

Boiler temperature<br />

Time<br />

Band limit<br />

Desired boiler / flow<br />

temp.<br />

Band limit<br />