Load and Transfer Instructions<br />

9.3 L STW Load Status Word into ACCU 1<br />

Format<br />

Description<br />

Status word<br />

Example<br />

L STW<br />

L STW (instruction L with the address STW) loads ACCU 1 with the contents of the<br />

status word. The instruction is executed without regard to, and without affecting, the<br />

status bits.<br />

Note<br />

For the S7-300 series CPUs, the statement L STW does not load the FC, STA, and<br />

OR bits of the status word. Only bits 1, 4, 5, 6, 7, and 8 are loaded into the<br />

corresponding bit positions of the low word of accumulator 1.<br />

BR CC 1 CC 0 OV OS OR STA RLO /FC<br />

writes: - - - - - - - - -<br />

<strong>STL</strong> Explanation<br />

L STW //Load contents of status word into ACCU 1.<br />

The contents of ACCU 1 after the execution of L STW is:<br />

Bit 31-9 8 7 6 5 4 3 2 1 0<br />

Content: 0 BR CC 1 CC 0 OV OS OR STA RLO /FC<br />

<strong>Statement</strong> <strong>List</strong> (<strong>STL</strong>) for S7-300 and S7-400 Programming<br />

9-4 A5E00706960-01