Word Logic Instructions<br />

13.7 XOD Exclusive OR Double Word (32-Bit)<br />

Format<br />

XOD<br />

XOD <br />

Address Data type Description<br />

DWORD,<br />

32-bit constant<br />

Description of instruction<br />

Status word<br />

Bit pattern to be combined with ACCU 1 by<br />

XOR (Exclusive Or).<br />

XOD (XOR double word) combines the contents of ACCU 1 with ACCU 2 or a 32-bit<br />

constant bit by bit according to the Boolean logic operation XOR (Exclusive Or). A bit<br />

in the result double word is "1" when only one of the corresponding bits of both<br />

double words combined in the logic operation is "1". The result is stored in ACCU 1.<br />

ACCU 2 remains unchanged. The status bit CC 1 is set as a result of the operation<br />

(CC 1 = 1 if result is not equal to zero). The status word bits CC 0 and OV are reset to<br />

0.<br />

You can use the Exclusive OR function several times. The result of logic operation is<br />

then "1" if an impair number of checked addresses ist "1".<br />

XOD: Combines ACCU 1 with ACCU 2.<br />

XOD : Combines ACCU 1 with a 32-bit constant.<br />

BR CC 1 CC 0 OV OS OR STA RLO /FC<br />

writes: - x 0 0 - - - - -<br />

<strong>Statement</strong> <strong>List</strong> (<strong>STL</strong>) for S7-300 and S7-400 Programming<br />