Timer Instructions<br />

Timer word<br />

for timer T1<br />

in memory<br />

Contents of<br />

ACCU1-L after<br />

Load instruction<br />

L T1<br />

2 15<br />

2 15<br />

2 14<br />

2 14<br />

2 13<br />

2 12<br />

2 11<br />

Time base<br />

00 = 10 ms<br />

01 = 100 ms<br />

10 = 1 s<br />

11 = 10 s<br />

2 13<br />

2 12<br />

All "0"<br />

2 11<br />

2 10<br />

2 10<br />

2 9<br />

2 9<br />

<strong>Statement</strong> <strong>List</strong> (<strong>STL</strong>) for S7-300 and S7-400 Programming<br />

12-8 A5E00706960-01<br />

2 8<br />

2 8<br />

2 7<br />

2 6<br />

2 5<br />

2 4<br />

2 3<br />

2 2<br />

2 1<br />

Time value (0 to 999) in binary coding<br />

2 7<br />

2 6<br />

L T1<br />

2 5<br />

2 4<br />

2 3<br />

2 2<br />

2 1<br />

Time value (0 to 999) in binary coding<br />

Note<br />

L loads only the binary code of the current timer value into ACCU1-L, and not<br />

the time base. The time loaded is the initial value minus the time elapsed since the<br />

timer was started.<br />

2 0<br />

2 0