10.15 Important Notes on Using MCR Functions<br />

!<br />

!<br />

Program Control Instructions<br />

Take care with blocks in which the Master Control Relay was activated with<br />

MCRA<br />

• If the MCR is deactivated, the value 0 is written by all assignments (T, =) in program<br />

segments between MCR( and )MCR.<br />

• The MCR is deactivated if the RLO was = 0 before an MCR( instruction.<br />

Danger: PLC in STOP or undefined runtime characteristics!<br />

The compiler also uses write access to local data behind the temporary variables<br />

defined in VAR_TEMP for calculating addresses. This means the following<br />

command sequences will set the PLC to STOP or lead to undefined runtime<br />

characteristics:<br />

Formal parameter access<br />

• Access to components of complex FC parameters of the type STRUCT, UDT, ARRAY,<br />

STRING<br />

• Access to components of complex FB parameters of the type STRUCT, UDT, ARRAY,<br />

STRING from the IN_OUT area in a block with multiple instance capability (version 2<br />

block).<br />

• Access to parameters of a function block with multiple instance capability (version 2<br />

block) if its address is greater than 8180.0.<br />

• Access in a function block with multiple instance capability (version 2 block) to a<br />

parameter of the type BLOCK_DB opens DB0. Any subsequent data access sets the<br />

CPU to STOP. T 0, C 0, FC0, or FB0 are also always used for TIMER, COUNTER,<br />

BLOCK_FC, and BLOCK_FB.<br />

Parameter passing<br />

• Calls in which parameters are passed.<br />

LAD/FBD<br />

• T branches and midline outputs in Ladder or FBD starting with RLO = 0.<br />

Remedy<br />

Free the above commands from their dependence on the MCR:<br />

1. Deactivate the Master Control Relay using the MCRD instruction before the statement or<br />

network in question.<br />

2. Activate the Master Control Relay again using the MCRA instruction after the statement<br />

or network in question.<br />

<strong>Statement</strong> <strong>List</strong> (<strong>STL</strong>) for S7-300 and S7-400 Programming<br />

A5E00706960-01 10-19