7<br />

SG4-E INSTRUCTION MANUAL<br />

Fig. 42 – T muting connection<br />

L muting<br />

In L type operation the device enters muting function if the inputs go high in a particular<br />

order: MUTING1 has to activate first, then MUTING2 can activate; if MUTING2 activates<br />

before MUTING1, the device doesn’t enter the muting function.<br />

“T12” is the activation delay between MUTING1 and MUTING2 that is selectable by the user<br />

by means of ACM.<br />

The muting function ends after a time that is a multiple of the activation delay between the<br />

two sensors (this time is m * T12). The value of “m” (T12 multiplier) can be chosen by the<br />

user. In BCM this value is 2 by default.<br />

The maximum activation delay between MUTING1 and MUTING2 can be set by the user<br />

from a minimum of 1 sec to a maximum of 16 sec. After this time if the user wants to enter in<br />

muting has to deactivate the muting input and start the sequence from the beginning.<br />

Fig. 43 – L muting timings<br />

42