A–6 Setting Up the DH-485 Network<br />

Configuring the SLC 5/03, SLC 5/04, and SLC 5/05 Channel 0 for<br />

DH485<br />

The RS-232 port (channel 0) of the SLC 5/03, SLC 5/04, and<br />

SLC 5/05 processor can be configured for DH485 protocol. Refer to<br />

your programming software user manual for software configuration<br />

information.<br />

You can connect channel 0 of the SLC 5/03, SLC 5/04, and<br />

SLC 5/05 processors to a DH485 network using the <strong>1747</strong>-CP3 cable<br />

and a 1761-NET-AIC Advanced Interface Converter (AIC+). In this<br />

case, the AIC+ must be powered with 24V dc. The 1746-P1, -P2,<br />

and -P4 power supplies provide 24V dc user power which may be<br />

used to power the AIC+.<br />

SLC 5/01<br />

SLC 5/04 or 5/05<br />

<strong>1747</strong>-AIC<br />

24V dc<br />

power<br />

supply<br />

DH-485<br />

<strong>1747</strong>-C11<br />

AIC+<br />

<strong>1747</strong>-CP3<br />

DH-485<br />

RS-232<br />

24V dc user power<br />

connection<br />

APS<br />

AIC+<br />

<strong>1747</strong>-CP3<br />

24V dc user power<br />

connection<br />

Publication <strong>1747</strong>-6.2