1–6<br />

Quick Start for Experienced Users<br />

7. Load your software. Reference<br />

Refer to your software package’s documentation. –<br />

8. Establish communications to the processor. Reference<br />

Follow the steps below:<br />

Chapter 8<br />

1. Refer to the following to establish communications between the processor and your personal<br />

(Starting Up Your<br />

Control System)<br />

computer.<br />

<strong>Processor</strong>: Procedure:<br />

SLC 5/01<br />

Connect <strong>1747</strong>-PIC from the processor to your personal computer.<br />

SLC 5/02<br />

Connect <strong>1747</strong>-PIC from the processor to your personal computer.<br />

SLC 5/03<br />

Connect <strong>1747</strong>-PIC from the processor to your personal computer or a <strong>1747</strong>-CP3 cable from<br />

channel 0 of the processor to the personal computer serial port.<br />

SLC 5/04<br />

Connect a <strong>1747</strong>-CP3 cable from channel 0 of the processor to the personal computer serial port<br />

or use a KT, KTX, KT2, or PCMK card.<br />

SLC 5/05<br />

Connect a <strong>1747</strong>-CP3 cable from channel 0 of the processor to the personal computer serial port.<br />

For Ethernet connection, connect channel 1 of the processor and the PC Ethernet Card to an<br />

Ethernet hub using 10Base-T cable.<br />

2. Set the communication parameters of software to match the default parameters of the processor:<br />

• SLC 5/01, SLC 5/02, and SLC 5/03 channel 1<br />

DH-485<br />

19.2K baud<br />

Node Address = 1<br />

• SLC 5/03 and SLC 5/04 only:<br />

channel 0 configuration:<br />

DF1 Full Duplex<br />

No Handshaking<br />

1200 baud<br />

CRC Error Check<br />

Duplicate Packet Detect On<br />

No Parity<br />

1 Stop Bit<br />

• SLC 5/04 only:<br />

channel 1 configuration:<br />

DH+<br />

57.6K baud<br />

Node Address = 1<br />

• SLC 5/05 only:<br />

channel 0 configuration:<br />

DF1 Full Duplex:<br />

No Handshaking<br />

19.2K baud<br />

CRC Error Check<br />

Duplicate Packet Detect On<br />

No Parity<br />

1 Stop Bit<br />

channel 1 configuration:<br />

Driver: Ethernet ➀<br />

➀ Configuring with BOOTP enabled so that a BOOTP server on the network can automatically provide the SLC 5/05 with the<br />

configuration necessary to start communicating over Ethernet. See Appendix G for more information.<br />

Publication <strong>1747</strong>-6.2