This appendix provides a brief introduction about control networks.<br />

For information on control networks, see the DCM User Manual,<br />

Catalog Number <strong>1747</strong>-NM007, RIO Scanner User Manual,<br />

Publication Number <strong>1747</strong>-6.6 and the DeviceNet Scanner<br />

Configuration Manual Publication Number <strong>1747</strong>-6.5.2.<br />

Allen-Bradley Remote I/O<br />

Network<br />

<strong>PLC</strong>-5 or SLC 5/02, SLC 5/03, or SLC 5/04<br />

proceesors with <strong>1747</strong>-SN scanner<br />

The Allen-Bradley Remote I/O Network is a master/slave control<br />

network that enables chassis of I/O, operator interface terminals,<br />

push-button panels, I/O blocks, message displays, drives and much<br />

more to be great distances from the host <strong>PLC</strong> processor. The SLC<br />

500 fixed, SLC 5/01, SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05<br />

can interface to this network through the <strong>1747</strong>-DCM module for<br />

distributed control. The DCM allows the SLC 500 to look like<br />

another device on the network.<br />

Below is an example of the Allen-Bradley Remote I/O Network.<br />

Fixed<br />

<strong>1747</strong>–DCM<br />

SLC 5/01<br />

<strong>1747</strong>–DCM<br />

SLC 5/03<br />

<strong>1747</strong>–DCM<br />

1771–Remote I/O Network<br />

PanelView<br />

Operator Terminal<br />

With the SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05 processor, a<br />

<strong>1747</strong>-SN Remote I/O Scanner can be used as the master of a remote<br />

I/O network. With a SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05<br />

and SN, a <strong>PLC</strong> is <strong>1747</strong> not required on the network. <strong>1747</strong><br />

<strong>1747</strong>–SN<br />

1771–Remote I/O Network<br />

PanelView<br />

Operator Terminal<br />

Block I/O<br />

<strong>1747</strong>–ASB<br />

<strong>1747</strong>–ASB<br />

Publication <strong>1747</strong>-6.2